AMT B1x-SAxxTE for active energy, single-tariff, up to 100 A
Three-phase static meters AMT B1x-SAxxTE for direct measurement of active electrical energy in single-tariff configuration up to 100 A.

Three-phase static meters AMT B1x-SAxxTE for direct measurement of active electrical energy in single-tariff configuration up to 100 A.
| Accuracy class | A or B (per MID), 2 or 1 (per EN 62053-21) |
|---|---|
| Reference voltage [V] | 3 x 220/380, 3 x 230/400, 3 x 240/415, 3 x 120/208, 3 x 57,7/100 (-30,+15%) |
| Nominal frequency [Hz] | 50 or 60 |
| Reference current Iref [A] direct connection | 5 and 10 |
| Nominal current In [A] indirect connection | 5 |
| Transitional current Itr [A] direct/indirect connection | 0,5 and 1 / 0,25 |
| Starting current Ist [A] direct/indirect connection | ≤ 0,02 and 0,04 / 0,01 |
| Minimum current Imin [A] direct/indirect conn. | 0,25 and 0,5 / 0,05 |
| Maximum current Imax [A] direct/indirect conn. | 100/10 |
| Power consumption - voltage circuit [VA/W] | ≤ 7,5/0,4 |
| Power consumption - current circuit(s) [VA] | ≤ 0,1 |
| Pulse constant for test output kTO [imp/kWh] | 1600 |
| Pulse constant for pulse output kSO [imp/kWh] | 1600 |
| Transistor output SO | 24 V / 30 mA |
| Operating temperature | - 40 °C to + 70 °C |
| Mean temperature coefficient [%/K] | ≤ 0,02 |
| Terminals current ; voltage ; auxiliary [mm] | ø 8 ; ø 3 ; ø 3 |
| Protection degree | IP54 |
| Number of tariffs | max. 2 |
| Mounting hole spacing - w x h [mm] | 150 x 215-230 |
| Dimensions - w x h/h´ x d [mm] | 177 x 187/251 x 60 |
| Weight [kg] | ≤ 1,30 |